Field Service Report Format No: BPE/CS/I&C-1-1PH 03 Ver 2.0
Customer Care Number : 1800 103 1247
BPE Electronic Services Pvt. Ltd. Email: support@bpeindia.com
G-215, Sector-63, Noida-201307 Uttar Pradesh Website: www.bpee.com
Customer Details Ticket Details
Customer Name and Address:AXIS BANK
Ground Floor, Shivalik-5, G-2B, Gondal Main Road, Near Makkam Chowk, Bhaktinagar, Rajkot, Gujarat, Pin 360002
Contact Person: USER Ticket ID: B23C07-000021
Contact No: 917069099935 Call Received
Date:
07 Mar 2023 10:54:55
Email ID: paneliya.rameshbhai@axisbank.com Call Closed
Date:
10 Mar 2023 10:20:43
Customer Complaint: UPS NOT WORKING Call Category: BREAKDOWN
Call Status: COMPLETED
Product Details
Product Name: Prodcut Category : Product Model: Product Capacity: Product Serial No: Unit Working Status :
ONLINE UPS 1PHASE/1PHASE PROSTAR 5KVA 5 RAJ0140 WORKING OK
Service and Observation
Observed Problem: today chek to ups working ok on row power mode check to battery backup 0 minit backup on battery mode found to 4 not battery faulty found and all battery set are 2016 and other ups battery is 2016 so 5 to 6 year old battery
Input Current Output Current Battery Current
L N E L E Charging Current Discharge Current
9 1 1 7 1 1.5 2.5
Input Voltage Output Voltage Battery Voltage
L-N E-N L-N E-N Charging Voltage Discharge Voltage after 3-5 Min
232 1.2 230 1 104 78
I/P Freq O/P Freq Display Information Other Fault observation if any:
Error Code With Description Load %
50 50 working 20% both ups battery are out of warranty and 5 to 6 year old both battery set are Parallel 8+8=16 connection second ups battery 8+8=16 both ups battery set required then propar backup battery is exide 12v 42ah betch code 4THO1211509766 and 4SJ010721009871
Battery Test Report
Battery Make: Battery Model: Battery AH: Nos. of Bank Ambient Temperature:
Exide SMF 42 1 21
Installed
Battery Position
from +(VE)
Batch Code Serial No Charging Voltage Battery Voltage Battery Voltage during Discharging Battery Status Faulty /OK/Week
After 2 Min After 5 Min After 10 Min After 20 Min Batter Low Before Cutoff
Total Voltage
Current
Connected Load Details:- sarver. pc printer.atm.etc..
Engineer Remarks on failure conclusion / Root Cause:- today chek to ups working ok on row power mode check to battery backup 0 minit backup on battery mode found to 4 not battery faulty found and all battery set are 2016 and other ups battery is 2016 so 5 to 6 year old battery
Replaced Spares if Any: no
Required Spares if Any: no
Serial No. Picture

10 Mar 2023 10:16:19
Display Picture

10 Mar 2023 10:16:32
Terminal Block Pucture

10 Mar 2023 10:17:09
Battery Bank Picture

10 Mar 2023 10:16:40
Faulty PCB/Spares/Section which have failure ovserved Photo

10 Mar 2023 10:17:53
Faulty PCB/Spares Barcode Picture
Battery Bank Picture

10 Mar 2023 10:16:40
Equipments Installation Position Picture
Customer Remarks:
Customer Picture

10 Mar 2023 10:20:35
Customer Name & Sign

Suraj sir
10 Mar 2023 10:20:08
Engineer Picture

10 Mar 2023 10:18:07
Engineer Name & Sign

CHAVDA RAJESHKUMAR GOBARBHAI
10 Mar 2023 10:17:57